Nemo 96 HD MF96001 IME

  • print
  • download

Mô tả sản phẩm

Tên sản phẩm
Nemo 96 HD MF96001 IME
MF96001
Hãng sản xuất
IME
Giá
Tình trạng
Có hàng
Flush mounting multifunction for low voltage

THÔNG TIN CHI TIẾT

Nemo 96 HD MF96001 IME
Connection via CT for single and three-phase network, 3 or 4-wires.
Phase sequence correction, diagnostic.
Can be accessorised with up to 4 additional modules.

Functions

• Phase and linked voltage
• Min. and max. phase voltage
• THDV
• Neutral and phase current
• Current demand and current max. demand
• Average current
• THDI
• Active, reactive phase power
• Power demand and power max. demand
• Positive and negative active and reactive energy
• Power factor
• Frequency
• Run hour meter, count start with voltage or power present

Cat. Nos.

Nemo 96 HD

Input (A)

Input* (V)

Auxiliary supply

Output

MF96001

1 + 5

80…500

80...265Vac

100...300Vdc

up 4 additional

modules

MF96002

1 + 5

80…500

16...60Vdc

up 4 additional modules


* Three-phase input 80…500V, Single -phase input 50…290V

Cat. Nos.

Additional modules

Descriptions

IF96001

Module RS485 Modbus RTU/TCP

IF96012

Module RS485 Modbus RTU/TCP + memory

IF96002

Module RS232 Modbus RTU/TCP

IF96007A

Module Profibus EN50170 - DP0

IF96009

Module LonWorks

IF96013

Module M-Bus EN1434-3

F96014

Module RS485 BACnet MS-TP

IF96015

Module Ethernet

IF96003

Module with 2 energy pulse outputs (SPST)

IF96004

Module with 2 x 0/4..20mA analogue outputs

IF96005

Module with 2 alarm relay outputs (SPST)

IF96006

Neutral current measurement from CT /1A or 5A programmable

F96016

Module temperature measurement 2 inputs from PT100

IF96010

Module with 2 input SPST-NO 2 relay outputs SPST-NO

IF96011

Module with 2 input 12/24Vcc 2 relay outputs SPST-NO

Input Nemo 96 HD MF96001 IME


  • Three-phase voltage (V): 80...500 (phase-phase)
  • Single-phase voltage (V): 50...290V
  • Current rating: 1A - 5A
  • External CT ratio: max 50kA/5A - max 10kA/1A
  • External VT ratio: primary voltage max 1200V
  • Continuous overload: 1,2In
  • Istantaneous overload: 20Imax/0,5s
  • Reference frequency: 50Hz
  • Frequency tolerance: 45...63Hz
  • Type of measurement: true RMS
  • Voltage rated burden (VA): ≤ 0,1VA (phase-neutral)
  • Current rated burden (VA): ≤ 1VA (for phase)

AUXILIARY SUPPLY Nemo 96 HD MF96001 IME


  • Rated value Uaux: 80...265Vac
  • Reference frequency: 50
  • Frequency tolerance: 45…63Hz)
  • Rated burden: ≤ 2,5VA (230Vac backlight 30% without external modules)
  • Rated value Uaux: 100...300Vdc 11...60Vdc
  • Rated burden: ≤ 3,5W (without modules)

ACCURACY Nemo 96 HD MF96001 IME


CONFORMITY ACCURACY WITH EN/IEC 61557-12:
- Voltage: cl.0,5
- Current: cl. 0,5
- Active energy: cl.0,5
- Reactive energy cl.2
- Active power cl.05
- Reactive power cl.1
- Apparent power cl.1
- Frequence cl.0,5
- Power factor cl.0,5
- THD cl.2

DISPLAY Nemo 96 HD MF96001 IME



  • Type of display: LCD backlighted
  • Digit height: 12mm
  • Energy resolution: depending on the CT/VT ratio**


MECHANICAL FEATURES Nemo 96 HD MF96001 IME


  • Housing: flush mounting (panel cutout 92x92mm)
  • Front frame: 96x96mm
  • Housing material: self-extinguishing polycarbonate
  • Protection degree: IP20 terminals/ IP54 front frame
  • Connections type: screw terminals
  • Rigid cable: max 4,5mm2
  • Flexible cable: max 2,5mm2


ENVIRONMENTAL CONDITIONS Nemo 96 HD MF96001 IME


  • Nominal temperature range: -5…55°C
  • Limit range for storage and transport: -25…70°C
  • Suitable for tropical climates: yes
  • Max.power dissipation*: ≤5W

* for switchboard thermal calculation
** kCT*kVT MAXIMUN DISPLAY
- 1...9 999999,99kWh/kvarh
- 10...99 9999999,9kWh/kvarh
- 100...999 99999999kWh/kvarh
- 1000...9999 999999,99MWh/Mvarh
- 10000...99999 9999999,9MWh/Mvarh
- 100000...400000 99999999MWh/Mvarh

OUTPUT Nemo 96 HD MF96001 IME


ADDITIONAL MODULES
  • N. max installable module: 1
  • Installation position: A-B-C-D

Bình luận