Nemo 96 HDLe MF96411 IME

  • print
  • download

Mô tả sản phẩm

Tên sản phẩm
Nemo 96 HDLe MF96411 IME
MF96411
Hãng sản xuất
IME
Giá
Tình trạng
Có hàng
Nemo 96 HDLe  Flush mounting multifunction for low voltage

THÔNG TIN CHI TIẾT

Nemo 96 HDLe MF96411 IME
Connection via CT for single and three-phase network, 3 or 4-wires.
Phase sequence correction, diagnostic
Can be accessorised with an additional modules.
It makes available active or reactive energy counting of the pulse output
to integration of consumption supervision systems.
For supervision systems, through the model with output RS485
communication ModbusRTU, you can transmitted on the network main
electrical parameters in addition to the energy consumption.

Functions

• Phase and linked voltage
• Min. and max. phase voltage
• THDV
• Voltage Harmonic analysis
• Voltage crest factor
• Neutral and phase current
• Current demand and current max. demand
• Average current
• THDI
• Current Harmonic analysis
• Current crest factor
• Active, reactive phase power
• Power demand and power max. demand
• Positive and negative active and reactive energy
• Power factor
• Frequency
• Run hour meter, count start with voltage or power present


Cat. Nos.

Nemo 96 HDLe

Input (A)

Input* (V)

Auxiliary supply

Output

MF96411

1 + 5

80…500

80...265Vac

100...300Vdc

Pulse + 1 additional

modules

MF96412

1 + 5

80…500

16...60Vdc

Pulse + 1 additional

modules

MF96421

1 + 5

80…500

80...265Vac

100...300Vdc

Pulse + RS485 ModBus

RTU/TCP + 1 additional

modules

MF96422

1 + 5

80…500

16...60Vdc

Pulse + RS485

ModBus RTU/TCP +

1 additional modules


* Three-phase input 80…500V, Single -phase input 50…290V

Cat. Nos.

Additional modules

Descriptions

IF96001

Module RS485 Modbus RTU/TCP

IF96012

Module RS485 Modbus RTU/TCP + memory

IF96002

Module RS232 Modbus RTU/TCP

IF96007A

Module Profibus EN50170 - DP0

IF96009

Module LonWorks

IF96013

Module M-Bus EN1434-3

F96014

Module RS485 BACnet MS-TP

IF96015

Module Ethernet



INPUT

  • Three-phase voltage (V): 80...500 (phase-phase)
  • Single-phase voltage (V): 50...290V
  • Current rating: 1A - 5A
  • External CT ratio: max 50kA/5A - max 10kA/1A
  • External VT ratio: primary voltage max 1200V
  • Continuous overload: 1,2In
  • Istantaneous overload: 20Imax/0,5s
  • Reference frequency: 50Hz – 400Hz (automatic selection)
  • Frequency tolerance: 45...65Hz (fn 50Hz) – 360...440Hz (fn 400Hz)
  • Type of measurement: true RMS
  • Harmonic content: up to the 50th harmonics
  • Voltage rated burden (VA): ≤ 0,1VA (phase-neutra)
  • Current rated burden (VA): ≤ 1VA (for phase)

AUXILIARY SUPPLY

  • Rated value Uaux: 80...265Vac
  • Reference frequency: 50 or 400Hz (automatic selection)
  • Frequency tolerance: 45…65Hz (fn 50Hz) or 360...440Hz (fn 400Hz)
  • Rated burden: ≤ 2,5VA (230Vac backlight 30% without external modules)
  • Rated value Uaux: 100...300Vdc
  • Rated burden: ≤ 3,5W (without modules, 110Vdc)

ACCURACY


CONFORMITY ACCURACY WITH EN/IEC 61557-12 :
- voltage: cl.0,5
- Current: cl. 0,5
- Active energy: cl.0,5
- Reactive energy cl.1
- Active power cl.05
- Reactive power cl.1
- Apparent power cl.1
- Frequence } 0,1Hz
- THD cl.1

DISPLAY

  • Type of display: LCD backlighted
  • Digit height: 8/12mm
  • Energy resolution: depending on the CT/VT ratio**

MECHANICAL FEATURES

  • Housing: flush mounting (panel cutout 92x92mm)
  • Front frame: 96x96mm
  • Housing material: self-extinguishing polycarbonate
  • Protection degree: IP20 terminals/ IP54 front frame
  • Connections type: screw terminals
  • Rigid cable: max 4,5mm2
  • Flexible cable: max 2,5mm2

ENVIRONMENTAL CONDITIONS

  • Nominal temperature range: -5…55°C
  • Limit range for storage and transport: -25…70°C
  • Suitable for tropical climates: yes
  • Max.power dissipation*: ≤5W

* for switchboard thermal calculation
** kCT*kVT MAXIMUN DISPLAY
- 1...9 999999,99kWh/kvarh
- 10...99 9999999,9kWh/kvarh
- 100...999 99999999kWh/kvarh
- 1000...9999 999999,99MWh/Mvarh
- 10000...99999 9999999,9MWh/Mvarh

Output


  • Type: Optorelay with potential-free
  • Contact range: 27 Vcc/ca-50mA
  • Assignable energy: Active or reactive energy
  • Pulse weight: selectable 10Wh/Varh...10MWh/MVarh
  • Pulse duration: selectable from 50 to 500ms

RS485 COMMUNICATION

  • Protocol: MODBUS RTU/TCP
  • Standard: RS485-3-wire
  • Baud rate: selectable 4800…38400 bit/s

ADDITIONAL MODULES

  • N. max installable module: 1
  • Installation position: A

Bình luận