Nemo 96 HDLe MF96412 Flush mounting multifunction for low voltage

THÔNG TIN CHI TIẾT

Nemo 96 HDLe MF96412 IME
Connection via CT for single and three-phase network, 3 or 4-wires.
Phase sequence correction, diagnostic
Can be accessorised with an additional modules.
It makes available active or reactive energy counting of the pulse output
to integration of consumption supervision systems.
For supervision systems, through the model with output RS485
communication ModbusRTU, you can transmitted on the network main
electrical parameters in addition to the energy consumption.

Functions

Phase and linked voltage
Min. and max. phase voltage
THDV
Voltage Harmonic analysis
Voltage crest factor
Neutral and phase current
Current demand and current max. demand
Average current
THDI
Current Harmonic analysis
Current crest factor
Active, reactive phase power
Power demand and power max. demand
Positive and negative active and reactive energy
Power factor
Frequency
Run hour meter, count start with voltage or power present


* Three-phase input 80…500V, Single -phase input 50…290V

INPUT

  • Three-phase voltage (V): 80...500 (phase-phase)
  • Single-phase voltage (V): 50...290V
  • Current rating: 1A - 5A
  • External CT ratio: max 50kA/5A - max 10kA/1A
  • External VT ratio: primary voltage max 1200V
  • Continuous overload: 1,2In
  • Istantaneous overload: 20Imax/0,5s
  • Reference frequency: 50Hz – 400Hz (automatic selection)
  • Frequency tolerance: 45...65Hz (fn 50Hz) – 360...440Hz (fn 400Hz)
  • Type of measurement: true RMS
  • Harmonic content: up to the 50th harmonics
  • Voltage rated burden (VA): ≤ 0,1VA (phase-neutra)
  • Current rated burden (VA): ≤ 1VA (for phase)

AUXILIARY SUPPLY

  • Rated value Uaux: 80...265Vac
  • Reference frequency: 50 or 400Hz (automatic selection)
  • Frequency tolerance: 45…65Hz (fn 50Hz) or 360...440Hz (fn 400Hz)
  • Rated burden: ≤ 2,5VA (230Vac backlight 30% without external modules)
  • Rated value Uaux: 100...300Vdc
  • Rated burden: ≤ 3,5W (without modules, 110Vdc)

ACCURACY

CONFORMITY ACCURACY WITH EN/IEC 61557-12 :
- voltage: cl.0,5
- Current: cl. 0,5
- Active energy: cl.0,5
- Reactive energy cl.1
- Active power cl.05
- Reactive power cl.1
- Apparent power cl.1
- Frequence } 0,1Hz
- THD cl.1

DISPLAY

  • Type of display: LCD backlighted
  • Digit height: 8/12mm
  • Energy resolution: depending on the CT/VT ratio**


MECHANICAL FEATURES

  • Housing: flush mounting (panel cutout 92x92mm)
  • Front frame: 96x96mm
  • Housing material: self-extinguishing polycarbonate
  • Protection degree: IP20 terminals/ IP54 front frame
  • Connections type: screw terminals
  • Rigid cable: max 4,5mm2
  • Flexible cable: max 2,5mm2

ENVIRONMENTAL CONDITIONS

  • Nominal temperature range: -5…55°C
  • Limit range for storage and transport: -25…70°C
  • Suitable for tropical climates: yes
  • Max.power dissipation*: ≤5W

* for switchboard thermal calculation
** kCT*kVT MAXIMUN DISPLAY
- 1...9 999999,99kWh/kvarh
- 10...99 9999999,9kWh/kvarh
- 100...999 99999999kWh/kvarh
- 1000...9999 999999,99MWh/Mvarh
- 10000...99999 9999999,9MWh/Mvarh

Output

  • Type: Optorelay with potential-free
  • Contact range: 27 Vcc/ca-50mA
  • Assignable energy: Active or reactive energy
  • Pulse weight: selectable 10Wh/Varh...10MWh/MVarh
  • Pulse duration: selectable from 50 to 500ms

RS485 COMMUNICATION

  • Protocol: MODBUS RTU/TCP
  • Standard: RS485-3-wire
  • Baud rate: selectable 4800…38400 bit/s

ADDITIONAL MODULES

  • N. max installable module: 1
  • Installation position: A

Bình luận